2 blocking findings · sign-off disabled

47 MCS rules checked against the calculation, survey, and provenance trail. 4 findings surfaced.

Findings

Sorted by severity. Click "Fix" to jump to the relevant survey field.

MAJOR
Heat-loss row per habitable room
BS-EN-12831.RoomSchedule.Coverage
Bedroom 3 missing from heat-loss schedule (visible in survey rooms list).
Fix: Add Bedroom 3 to the room schedule before sign-off.
WARN
Neighbour distance recorded
MCS-020.NoiseAssessment.NeighbourDistance
neighbour_distance_m is null on Survey object.
Fix: Capture distance to nearest neighbour habitable window.
MAJOR
Emitter delivers ≥ recommended W at flow temp
EmitterCheck.RadiatorOversize
Living Room calc recommends 1,420 W; existing emitter delivers 980 W at 45°C flow.
Fix: Upsize Living Room radiator to type 22 1200×600 minimum.
WARN
Cylinder volume meets occupant demand
DHW.CylinderSize
Cylinder 170L for 4 occupants — borderline (45 L × 4 + 50 L = 230 L target).
Fix: Recommend 210L–250L cylinder upsize.

Calculation summary

BS EN 12831 · MCS 020 · MCS 031 · SCOP estimate

Total heat loss
9.21 kW
at -2.1°C design outdoor
SCOP estimate
3.8
at 45°C flow / 35°C design
Capture method
video
Provenance recorded